Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Electric Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
No. | Item | Unit | Data | ||||
1 | Rated voltage | kV | 24 | ||||
2 | Rated insulation level | 1min P.F withstand voltage | Dry test | 65/79(isolating distance) | |||
Wet test | 50/64(isolating distance) | ||||||
Auxiliary loop and control loop | 2 | ||||||
Lightning impulse withstand voltage(peak) | 125/145(isolating distance) | ||||||
3 | Rated frequency | Hz | 50/60 | ||||
4 | Rated current | A | 630,1250 | ||||
5 | Rated operating sequence | O-0.3s-CO-180s-CO | |||||
6 | Rated short-circuit breaking current | kA | 16 | 20 | 25 | ||
7 | Rated short-circuit making current(peak) | 40 | 50 | 63 | |||
8 | Rated peak withstand current(peak) | 40 | 50 | 63 | |||
9 | Rated short-time withstand current | 16 | 20 | 25 | |||
10 | Rated short-circuit duration | s | 4 | ||||
11 | Breaking times of rated current | times | 1000 | ||||
12 | Breaking times of rated short-circuit breaking current | 20 | |||||
13 | Closing time | ms | 20~80 | ||||
14 | Opening time | At max. operating voltage | 20~80 | ||||
At rated operating voltage | 20~80 | ||||||
At min. operating voltage | 20~80 | ||||||
15 | Complete breaking time | ≤100 | |||||
16 | Mechanical life | times | 10000 | ||||
17 | Closing power | J | 70 | ||||
18 | Rated input power for energy storage motor | W | ≤70 | ||||
19 | Rated operating voltage and rated auxiliary loop current | V | DC/AC220 | ||||
20 | Energy storage time under rated voltage | S | ≤8 | ||||
21 | Over-current tripping device | Rated current | A | 5 | |||
Tripping current accuracy | % | ±10 | |||||
22 | Average opening speed | m/s | 1.5±0.2 | ||||
23 | Average closing speed | 0.8±0.2 | |||||
24 | Contact close-boucing time | ms | ≤3 | ||||
25 | Three-phase opening non-simultaneity | ≤2 | |||||
26 | DC resistance for each phase loop(with isolator) | μΩ | ≤80(150 with isolator) | ||||
27 | Allowed accumulative wear thickness for moving and static contacts | mm | 3 | ||||
28 | Phase-to-phase spacing | 390±1.5 | |||||
29 | Contact self-closing pressure | N | 2000±200 | ||||
30 | Net weight | kg | 125(155 with isolator) |