Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Energy-storage Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Item
|
Unit
|
Parameter
|
|||
Rated voltage
|
kV
|
12
|
|||
Maximum operating voltage
|
Hz
|
12 | |||
Rated current
|
A
|
630
|
1250
|
1600
|
|
Ratedshort-circuit breakingcurrent
|
kA
|
20 |
25
|
31.5
|
|
Ratedshort-circuit closingcurrent
|
kA
|
50
|
63
|
80
|
|
Ratedshort-circuit closingcurrent
|
kA
|
50
|
63
|
80
|
|
4S rated short-circuit withstand current
|
kA
|
20
|
25 |
31.5
|
|
Rated
insulation level
|
Power frequency withstand voltage
(before and after rated breaking)
|
kV |
42(Break48)
|
||
Impact withstand voltage (before and afterrated breaking) |
75(Break85)
|
||||
Ratedsequenceofoperations
|
0-0.3s-C0-180s-CO
|
Item
|
Unit
|
Parameter
|
|||
Mechanical life
|
times
|
30000
|
|||
Rated number of short circuit breaking current breaks
|
times
|
50
|
|||
Operating mechanism rated closing voltage(DC)
|
V
|
110,220
|
|||
Operating mechanism rated opening voltage(DC)
|
V
|
110,220
|
|||
Contact spacing
|
mm
|
11±1
|
|||
Overtravel(contact spring compression length)
|
mm
|
3.5±0.5
|
|||
Three-phase division,closing bounce time
|
ms
|
≤2
|
|||
Contact closure bounce time
|
ms
|
≤2
|
|||
Average opening speed
|
m/s
|
0.9±1.2
|
|||
Average closing speed
|
m/s
|
0.4±0.8
|
|||
Opening time
|
At the highest operating voltage
|
s |
≤0.05
|
||
At the lowest operating voltage
|
≤0.08
|
||||
Closing time
|
0.1
|
||||
The main loop resistance of each phase
|
Ω
|
60 50
|