Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Electric Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
No. | Item | Unit | Data | ||||
1 | Rated voltage | kV | 40.5 | ||||
2 | Rated insulation level | 1min P.F withstand voltage |
Dry test | 95 | |||
Wet test | 80 | ||||||
Lighting impulse withstand voltage(peak) | 185 | ||||||
3 | Rated current | A | 630,1250,1600,2000 | ||||
4 | Rated short-circuit breaking current | kA | 20 | 25 | 31.5 | ||
5 | Rated short-circuit making current (peak) | 50 | 63 | 80 | |||
6 | Rated operating sequence | O-0.3s-CO-180s-CO | |||||
7 | Rated short-time withstand current | kA | 20 | 25 | 31.5 | ||
8 | Rated peak withstand current | 50 | 63 | 80 | |||
9 | Rated short-circuit duration | s | 4 | ||||
10 | Rated operating voltage | V | DC/AC220 | ||||
11 | Breaking times of rated short-circuit breaking current | times | 12 | ||||
12 | Complete breaking time | ms | ≤80 | ||||
13 | Mechanical s life | times | 10000 | ||||
14 | Average opening speed | m/s | ≥1.4 | ||||
15 | Average speed of closing | ≥0.4 | |||||
16 | Contact close-bouncing time | ms | ≤5 | ||||
17 | Three-phase opening non-simultaneity | ≤2 | |||||
18 | Opening time | ms | ≤60 | ||||
19 | Closing time | ≤90 | |||||
20 | DC resistance for each phase loop | µΩ | ≤100 | ||||
21 | Phase-to-phase spacing | mm | 710 | ||||
22 | Allowed accumulative wear thickness for moving and static contacts | 3 | |||||
23 | Dimension (length×width×height) | 2080×500×2275 | |||||
24 | Contact self-closing pressure | N | 2500 | ||||
25 | Net weight | kg | 800/740 |