Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Energy-storage Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
ltem | Unit | Data | ||
FN12-12D/630 | FN12-12(R)D/630 | |||
1 | Rated voltage | KV | 12 | |
2 | Rated frequency | Hz | 50 | |
3 | Rated current | A | 630 | 100 |
4 | Lightning impulse withstand voltage | KV | To earth and phase to phase75,isolating fracture 85 | |
5 | l min power frequency withstand voltage | KV | To earth and phase to phase 42,isolating fracture 48 | |
6 | Rated thermal stability current | KA | 20 (4S) | |
7 | Rated dynamic current | KA | 50 | |
8 | Rated closing current (peak | KA | 50 | 50 |
9 | Rated short circuit breaking current (Expected value) | KA | 31.5 | |
10 | Maximum at critical breaking current | A2S | According to the fuse characteristic curve | |
11 | Minimum breaking current | KA | According to the fuse characteristic curve | |
12 | Rated transfer current | KA | 1.5 | |
13 | Maximum breaking current (reference value) | KA | 1.8 | |
14 | Breaking the capacity of the no-load transformer | KVA | 1250 | |
15 | Rated cable charging curren | A | 10 | |
16 | Rated active load current breaking times | Times | >100 | |
17 | The impactor touches the load switch opening time | S | >0.06 | |
18 | Earthing switch thermal stability curren | KA | 20(2S) | |
19 | Earthing switch thermal stability current (peak | KA | 50 | |
20 | Motor operating power supply voltage | V | AC DC 110,220 |