Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Electric Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Item | Unit | Data | Note | ||
Rated voltage | kV | 12/40.5 | |||
Rated current | A | 630 | 1250 | ||
Rated peak withstand current | kA | 50 | 80 | ||
4s short-time withstand current | 20 | 31.5 | |||
Rated static pull on connection terminal | N | 735 | |||
Rated power frequency | Hz | 50/60 | |||
1min power frequency withstand voltage | kV | Phase to phase, phase to earth: 185/275 | Suitable for three pole linkage |
||
across open contacts: 210/315 | |||||
Lightning impulse withstand voltage(peak) | kV | Phase to phase, phase to earth: 450/650 across open contacts: 520/750 |
Suitable for three pole linkage |
||
Weight of switchbody | kg | ≈240 | |||
Operating mechanism | CS14 manual | ||||
Earth method | Without earth, single earth, double earth | ||||
Post insulate creepage distance | mm | Normal type: 1870 anti-pollution: 3050 | |||
With earth switch | Short-time withstand current | kA | 12.5(2s) | 20(2s) | |
Peakwithstand current | 31.5 | 50 |