Customization: | Available |
---|---|
Type: | Low-voltage |
Structure: | Three-column Disconnector |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Parameter name
|
Parameter value
|
Rated operating voltage (Ue), V
|
ВР32-Ф; ВР32
|
Alternating current.
|
380, 660
|
Direct current.
|
220, 440
|
Rated insulation voltage (Ui), V
|
660
|
Conditional thermal current in open air (Ith), A.
|
100; 250; 400; 630
|
Conditional thermal current for devices embedded in enclosures (Ithe), A.
|
80; 200; 315; 500
|
Mechanical wear resistance, cycles VO. - For a current of 100 and 250 A - For a current of 400 and 630 A |
25000
16000
|
Cross-section of connected conductors, mm2 - For a current of 100 A - For a current of 250 A - For a current of 400 A - For a current of 630 A |
10...50 70...150 120...3х120 150...4х120 |
Application categories |
АС-21 V, АС-22 V - with cameras
АС-20 V - no cameras,
|
Degree of protection
|
IP00
|
Number of auxiliary contacts (per device) per direction
|
One (1 opening, 1 closing).
|
In two directions. |
Two
|
Rated operating current (Ie), A
|
2,5
|
Rated operating voltage 50 Hz (Ue), V
|
220
|
Application category
|
АС-15; DC-13
|
Characteristics under short-circuit conditions
|
Conditional thermal current of the device, A. 100 250 400 630 |
Rated short-time withstand current, kA
|
5 8 11 16 |
Rated conditional short-circuit current, kA
|
8 14 22 32 |